Operation Theory 45
Delay Trigger Acquisition
Use delay trigger acquisition in applications where you want to delay the data
collection after the occurrence of a specified trigger event. The delay time is
controlled by the value, which is pre-loaded in the Delay_counter (16bit). The
counter counts down on the rising edge of Delay_counter clock source after
the trigger condition is met. The clock source can be software programmed
either Timebase clock (24MHz) or A/D sampling clock (Timebase
/SI2_counter). When the count reaches 0, the counter stops and 9116 card
starts to acquire data. The total acquired data length = DIV_counter *
SC_counter.
(DIV_Counter=4, SC_Counter=3)
Acquisition_in_progress
Scan_start
AD_conversion
Scan_in_progress
(SSH_OUT)
Acquired & stored data
(3 scans)
Operation start
ExtTrg
Delay until
Delay_Counter
reaches 0
Figure 17: Delay trigger
Note: When the Delay_counter clock source is set to Timebase, the
maximum delay time = 2
16
/24M s = 2.73ms, and when the source is
set to A/D sampling clock, the maximum delay time = 2
16
*
SI2_counter / 24M).
Zobrazit stránku 54